Apiste Panel Cooling Units Standard ENC-GS620L, GS1120L, GS-1652L, GS2200L, GS2900L, GS352WL, G310L, G320L, G451S, G610L, G1110L, G1651L
Xuất sứ: Apiste
Nhà cung cấp: PITESCO Viet Nam
Hãng sản xuất: Apiste
ENC-GS620L
Specifications
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 580/580 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 55 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H450×W350×D250 |
Volume (kg) | 19 |
Coating Color | Munsell 5Y7/1 Equivalent color of light beige |
Voltage Rating (V) | Single-phase AC200 to 240 |
Consumption Current/Rating (A) | 2.7 / 2.6 |
Consumption Current/MAX (A) | 3.3 / 3.2 |
Inrush current (A) | 150 (Application time : 6ms) |
Consumption Voltage/Rating (W) | 415 |
Consumption Voltage/MAX (W) | 520 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a / 145 |
Noise (dB) | Approx. 68 |
External Output | Alarm output (Rated voltage nomally open : 250VAC 2A) The change to normal close is possible. |
Display | Panel internal temperature / Error code, RUN |
Environmental Response | RoHS |
ENC-GS1120L
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 1080/1080 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 55 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H730×W300×D260 |
Volume (kg) | 24 |
Coating Color | Munsell 5Y7/1 Equivalent color of light beige |
Voltage Rating (V) | Single-phase AC200 to 240 |
Consumption Current/Rating (A) | 4.1 / 3.8 |
Consumption Current/MAX (A) | 4.4 / 4.4 |
Inrush current (A) | 150 (Application time : 6ms) |
Consumption Voltage/Rating (W) | 640 |
Consumption Voltage/MAX (W) | 730 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a / 235 |
Noise (dB) | Approx. 71 |
External Output | Alarm output (Rated voltage nomally open : 250VAC 2A) The change to normal close is possible. |
Display | Panel internal temperature / Error code, RUN |
Environmental Response | RoHS |
ENC-GS1652L
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 1630/1630 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 55 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H1000×W400×D230 |
Volume (kg) | 35 |
Coating Color | Munsell 5Y7/1 Equivalent color of light beige |
Voltage Rating (V) | Single-phase AC200 to 240 |
Consumption Current/Rating (A) | 4.6 / 4.5 |
Consumption Current/MAX (A) | 5.9 / 5.8 |
Inrush current (A) | 150 (Application time : 6ms) |
Consumption Voltage/Rating (W) | 735 |
Consumption Voltage/MAX (W) | 960 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a / 540 |
Noise (dB) | Approx. 70 |
External Output | Alarm output (Rated voltage nomally open : 250VAC 2A) The change to normal close is possible. |
Display | Panel internal temperature / Error code, RUN |
Environmental Response | RoHS |
ENC-GS2200L
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 2245/2245 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 55 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H1200×W450×D230 |
Volume (kg) | 43 |
Coating Color | Munsell 5Y7/1 Equivalent color of light beige |
Voltage Rating (V) | Single-phase AC200 to 240 |
Consumption Current/Rating (A) | 5.3 / 5.2 |
Consumption Current/MAX (A) | 7.1 / 6.9 |
Inrush current (A) | 150 (Application time : 6ms) |
Consumption Voltage/Rating (W) | 870 |
Consumption Voltage/MAX (W) | 1170 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a / 615 |
Noise (dB) | Approx. 72 |
External Output | Alarm output (Rated voltage nomally open : 250VAC 2A) The change to normal close is possible. |
Display | Panel internal temperature / Error code, RUN |
Environmental Response | RoHS |
ENC-GS2900L
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 2840/2840 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 55 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H1200×W450×D230 |
Volume (kg) | 45 |
Coating Color | Munsell 5Y7/1 Equivalent color of light beige |
Voltage Rating (V) | Single-phase AC200 to 240 |
Consumption Current/Rating (A) | 6.8 / 6.5 |
Consumption Current/MAX (A) | 7.2 / 7.0 |
Inrush current (A) | 150 (Application time : 6ms) |
Consumption Voltage/Rating (W) | 1110 |
Consumption Voltage/MAX (W) | 1200 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a / 780 |
Noise (dB) | Approx. 76 |
External Output | Alarm output (Rated voltage nomally open : 250VAC 2A) The change to normal close is possible. |
Display | Panel internal temperature / Error code, RUN |
Environmental Response | RoHS |
ENC-G352WL
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 300/350 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H280×W450×D150 |
Volume (kg) | 14 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 1.8/1.4 |
Consumption Current/MAX (A) | 2.0/1.8 |
Starting Current (A) | 4.0/4.2 |
Consumption Voltage/Rating (W) | 280/260 |
Consumption Voltage/MAX (W) | 350/340 |
Noise Resistance | VCCI Class A compliance |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 80g |
Noise (dB) | 60/63 |
Display | Power indicator (Green) |
Regulatory Compliance | Electrical Appliance and Material Safety Law |
Parts list supplied
Mounting Bolt | 4 (M6 x L20) |
---|---|
Exhaust Hose | 2m |
INSULOK Tie | 1 |
Washer | 2 |
Spacer | 4 |
Mounting nut | 4(M6) |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G352WL |
---|---|
External Fan | Air fan for G352WL |
Filter | ENC-F-32 * 2 |
ENC-G310L
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 280/300 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H590×W200×D200 |
Volume (kg) | 15 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 3.4/3.2 |
Consumption Current/MAX (A) | 3.7/3.8 |
Starting Current (A) | 7.4/7.7 |
Consumption Voltage/Rating (W) | 290/310 |
Consumption Voltage/MAX (W) | 330/370 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | R-134a 85g |
Noise (dB) | 65/68 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 6 (M6 × L20) |
---|---|
Exhaust Hose | 2m |
INSULOK Tie | 1 |
Spacer | 6 |
Gland | (Length) 2/ (short) 2 |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G310L |
---|---|
External Fan | Air fan for G310L |
Filter | ENC-F-38 * 2 |
Electrical Board | Substrate for G310L/G320L |
ENC-G320L
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 280/300 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H590×W200×D200 |
Volume (kg) | 15 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 1.8/1.5 |
Consumption Current/MAX (A) | 2.0/1.8 |
Starting Current (A) | 4.0/4.2 |
Consumption Voltage/Rating (W) | 280/260 |
Consumption Voltage/MAX (W) | 340/320 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | R-134a 85g |
Noise (dB) | 65/68 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 6 (M6 x L20) |
---|---|
Exhaust Hose | 2m |
INSULOK Tie | 1 |
Spacer | 6 |
Gland | (Length) 2/ (short) 2 |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G320L |
---|---|
External Fan | Air fan for G320L |
Filter | ENC-F-38 * 2 |
Electrical Board | Substrate for G310L/G320L |
ENC-G451S
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 400/450 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 25 to 45 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H450×W300×D115 |
Volume (kg) | 13 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 3.4/3.2 |
Consumption Current/MAX (A) | 3.6/3.7 |
Starting Current (A) | 7.4/7.7 |
Consumption Voltage/Rating (W) | 280/300 |
Consumption Voltage/MAX (W) | 320/360 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | R-134a 90g |
Noise (dB) | 59/62 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 6 (M6 x L20) |
---|---|
Exhaust Hose | 2m |
INSULOK Tie | 1 |
Spacer | 6 |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G451S |
---|---|
External Fan | Air fan for G451S |
Filter | ENC-F-35 * 2 |
Electrical Board | Substrate for AR451S/AR452S |
ENC-G610L
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 500/600 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H450×W350×D200 |
Volume (kg) | 16 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 3.3/3.2 |
Consumption Current/MAX (A) | 3.9/4.1 |
Starting Current (A) | 7.4/7.7 |
Consumption Voltage/Rating (W) | 270/310 |
Consumption Voltage/MAX (W) | 340/370 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 100g |
Noise (dB) | 63/67 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 6 (M6 x L20) |
---|---|
Exhaust Hose | 2m |
INSULOK Tie | 1 |
Washer | 2 |
Spacer | 6 |
Wind Direction Louver | 1 |
Louvered Screw | 2 |
Gland | (Length) 2/ (short) 2 |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G610S |
---|---|
External Fan | Air fan for G610S |
Filter | ENC-F-23 * 2 |
Electrical Board | Substrate for G610L/G620L |
ENC-G1110L
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 950/1100 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H730×W300×D230 |
Volume (kg) | 23 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 5.5/4.8 |
Consumption Current/MAX (A) | 6.7/6.8 |
Starting Current (A) | 15.6/14.7 |
Consumption Voltage/Rating (W) | 450/470 |
Consumption Voltage/MAX (W) | 620/680 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 230g |
Noise (dB) | 64/68 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 6 (M6 x L20) |
---|---|
Exhaust Hose | 2m |
INSULOK Tie | 1 |
Washer | 2 |
Spacer | 6 |
Wind Direction Louver | 1 |
Louvered Screw | 2 |
Gland | (Length) 2/ (short) 2 |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G1110L |
---|---|
External Fan | Air fan for G1110L |
Filter | ENC-F-21 * 2 |
Electrical Board | Substrate for G1110L/G1120L |
ENC-G1651L
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 1450/1650 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 55 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H1000×W400×D230 |
Volume (kg) | 38 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 7.0/6.7 |
Consumption Current/MAX (A) | 8.5/9.0 |
Starting Current (A) | 22.3/20.5 |
Consumption Voltage/Rating (W) | 580/650 |
Consumption Voltage/MAX (W) | 740/870 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | JIS Z 0200 Level1 |
Coolant / Filling (g) | R-407c 400g |
Noise (dB) | 68/72 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 6 (M8 x L25) |
---|---|
Exhaust Hose | 2m |
INSULOK Tie | 1 |
Washer | 2(M6) |
Spacer | 6 |
Wind Direction Louver | 1 |
Louvered Screw | 2 |
Mounting nut | 2(M8) |
Double-ended Screw | 2(M8) |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G1651L |
---|---|
External Fan | Air fan for G1651L |
Filter | ENC-F-45 * 2 |
Electrical Board | Substrate for G1651L/G1652L |