Function

Type          :  Temperature Transmitter(TIT), Field Mounting Type
Certificate :   Ex d, FM, ATEX, TR CU(EAC), CE, KCs, IP66/67.

                      Feature4 to 20mA, HART, Loop Powered

                      Digital Accuracy: RTD ±0.17 ℃ , T/C ±0.77 ℃

                      3 lines LCD display, Self Diagnostic Function, External Buttons, DAC, Zero Trim, Eng mode

InputRTD input: a=0.00385(KS, JIS, DIN, IEC), a=0.00391(US)

Thermocouple input: KSC 1602-1982, JISC 1602-1981, ANSI MC96.1-1982

Millivolt, ohms

ApplicationPressure: Flow, Level measurement for Oil & Gas, Liquid, Water, Maine & offshore, Vessel, Power, Chemical Plants and Refinary

Specification

Model Name

 

ATT2100

Protocol

 

Digital Communication, HART 5, 7

Trim ability

 

Zero, DAC

Power supply & Load Requirement

 

250 to 550 ohm @ 24 Vdc, Loop Powered

Falure Mode

 

Low ≤ 3.78 mA, High ≥ 21.1 mA

External Buttons

 

Zero & Span 2 buttons for device configuration

Ambient Temp. limit

 

-40 to 85℃ ( -104 to 185℉ )

Stability

 

RTD – 2 years (±0.12% of Reading or 0.15℃ whichever is greater),

 

 

T/C – 1 years (±0.12% of Reading or 0.15℃ whichever is greater)