brauntacho-vietnam-protection-systems-single-channel-for-1oo1-1oo2-and-2oo2-solutions-triple-channel-tmr-for-2oo3-solutions-oem-specific-protection-systems-brauntacho-viet-nam-1.png

E16 System product matrix (overview), Standard solutions in 2oo3 architecture

Model SIL3 SIL2 PFD Value Test
Interface
Test
Generator
Automatic
Test of 2oo3
Solenoid
by E16
PROFIBUS
Interface
E16x342 ●   7,71 · 10-5 ●     1
E16x352 ●   7,71 · 10-5 ●     2
E16x346 ●   8,41 · 10-6   ● ● 1
E16x356 ●   8,41 · 10-6   ● ● 2
E16x442   ● 1,81 · 10-4 ●     1
E16x452   ● 1,81 · 10-4 ●     2
E16x446   ● 2,51 · 10-5   ● ● 1
E16x456   ● 2,51 · 10-5   ● ● 2

Protection Systems for highest safety requirements up to SIL 3

E16x342

Monitoring and Protection System E16x342 for highest safety requirements up to SIL3

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • External test of a 2oo3 solenoid valve block possible via the control system
  • Minimal Total Cost of Ownership
  • Requires less than 8% of the permissible PFD value for a SIL3 Safety Loop
  • Replacement of all active components during operation (Hot Swap)
  • TÜV certified for SIL3 / IEC 61508:2010
  • TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
  • TÜV certified for SILCL3 / IEC 62061:2005
  • API670 and API612 compliant
  • 1 PROFIBUS Interface

E16x352

Monitoring and Protection System E16x352 for highest safety requirements up to SIL3

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • External test of a 2oo3 solenoid valve block possible via the control system
  • Minimal Total Cost of Ownership
  • Requires less than 8% of the permissible PFD value for a SIL3 Safety Loop
  • Replacement of all active components during operation (Hot Swap)
  • TÜV certified for SIL3 / IEC 61508:2010
  • TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
  • TÜV certified for SILCL3 / IEC 62061:2005
  • API670 and API612 compliant
  • 2 PROFIBUS Interfaces

E16x346

Monitoring and Protection System E16x346 for highest safety requirements up to SIL3

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
  • Minimal Total Cost of Ownership
  • Requires less than 1% of the permissible PFD value for a SIL3 Safety Loop
  • Enhanced safety values due to an integrated test generator
  • Replacement of all active components during operation (Hot Swap)
  • TÜV certified for SIL3 / IEC 61508:2010
  • TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
  • TÜV certified for SILCL3 / IEC 62061:2005
  • API670 and API612 compliant
  • 1 PROFIBUS Interface

E16x356

Monitoring and Protection System E16x356 for highest safety requirements up to SIL3

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
  • Minimal Total Cost of Ownership
  • Requires less than 1% of the permissible PFD value for a SIL3 Safety Loop
  • Enhanced safety values due to an integrated test generator
  • Replacement of all active components during operation (Hot Swap)
  • TÜV certified for SIL3 / IEC 61508:2010
  • TÜV certified for PL e; Cat. 3 / DIN EN ISO 13849-1:2008
  • TÜV certified for SILCL3 / IEC 62061:2005
  • API670 and API612 compliant
  • 2 PROFIBUS Interfaces

E16x442

Monitoring and Protection System E16x442 for increased safety requirements up to SIL2

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • External test of a 2oo3 solenoid valve block possible via the control system
  • Minimal Total Cost of Ownership
  • Requires less than 8% of the permissible PFD value for a SIL2 Safety Loop
  • Replacement of all active components during operation (Hot Swap)
  • SIL2 / IEC 61508:2010 compliant
  • API670 and API612 compliant
  • 1 PROFIBUS Interface

E16x452

Monitoring and Protection System E16x452 for increased safety requirements up to SIL2

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • External test of a 2oo3 solenoid valve block possible via the control system
  • Minimal Total Cost of Ownership
  • Requires less than 8% of the permissible PFD value for a SIL2 Safety Loop
  • Replacement of all active components during operation (Hot Swap)
  • SIL2 / IEC 61508:2010 compliant
  • API670 and API612 compliant
  • 2 PROFIBUS Interfaces

E16x446

Monitoring and Protection System E16x446 for increased safety requirements up to SIL2

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
  • Minimal Total Cost of Ownership
  • Requires less than 1% of the permissible PFD value for a SIL2 Safety Loop
  • Enhanced safety values due to an integrated test generator
  • Replacement of all active components during operation (Hot Swap)
  • SIL2 / IEC 61508:2010 compliant
  • API670 and API612 compliant
  • 1 PROFIBUS Interface

E16x456

Monitoring and Protection System E16x456 for increased safety requirements up to SIL2

  • TMR (triple-modular-redundant) system with sensor monitoring and self-test
  • Highest safety levels with maximum availability by globally unique and true 2oo3 architecture for each trip criterion within each of the three Monitors
  • Maintenance-free during lifetime due to integrated automatic proof tests
  • Automated tests of a 2oo3 solenoid valve block with permanent monitoring of the feedback via the test generator
  • Minimal Total Cost of Ownership
  • Requires less than 1% of the permissible PFD value for a SIL2 Safety Loop
  • Enhanced safety values due to an integrated test generator
  • Replacement of all active components during operation (Hot Swap)
  • SIL2 / IEC 61508:2010 compliant
  • API670 and API612 compliant
  • 2 PROFIBUS Interfaces