dpt-dual-mod-hk-instruments-vietnam.png

DPT-Dual-MOD HK Instruments Vietnam

Field adjustable differential pressure transmitter with two pressure sensors for air and an Input terminal for two analog inputs for external signal conversion into Modbus.

DPT-Dual-MOD combines two differential pressure transmitters into one device. It offers a possibility to measure pressure from two different points. It has a Modbus interface and an Input terminal. When using the Input terminal, temperature transmitters can be replaced with temperature sensors. As a result you will save in costs of the devices and in the installation costs. The AHU model that includes an air flow transmitter has been designed especially for ventilation units.

DPT-Dual-MOD series devices include:
• Multiple measurement units, field selectable via menu, including: Pa, mbar, inchWC, mmWC and psi.
• Input terminal enabling reading of multiple other signals such as temperature or control relays over Modbus

Technical details

Communication: RS-485 Modbus (RTU)
Accuracy (from applied pressure): 
(model 2500)
Pressure < 125 Pa = 1 % + ±2 Pa
Pressure > 125 Pa = 1 % + ±1 Pa
Accuracy (from applied pressure): 
(model 7000)
Pressure < 125 Pa = 1.5 % + ±2 Pa
Pressure > 125 Pa = 1.5 % + ±1 Pa
Zero point calibration: via Modbus or by pushbutton
Measuring units: Pressure: Pa, kPa, mbar, inchWC, mmWC, psi
Flow: (AHU model) m3/s, m3/hr, cfm, l/s, m/s, ft/min
Supply voltage: 24 VDC ±10 % / 24 VAC ±10 %
Power consumption: < 1.3 W
Operating temperature: -10…+50 °C
Response time: 1...20 s selectable via menu
Protection standard: IP54

DPT-Dual-MOD

Example 
DPT-Dual-MOD-2500-D

Model

Product series

DPT
Differential pressure transmitter
DPT

Model type

-Dual-MOD
Two pressure sensors and Modbus communication
-Dual-MOD

Measuring ranges (Pa)

-2500
-250...2500
-7000
-250...7000
-AHU
both 2500 and 7000 sensors, with flow measurement
-2500

Display

-D
With display
-D