ACT-016 Series is motor actuated proportional damper actuator controlled by the signal DC 0~10V or 4 ~ 20mA, and designed for damper control in HVAC system and can provide 0 ~10V position feed back signal.

 
Used for operating Damper for ventilation and Air handling facilities.
Nominal torque is 20Nm and can be covered damper surface area for 3㎡.
Proportional operation will be activated by DC 0 ~10V or 4 ~ 20mA and possible to be DC 0 ~   
  10V position feedback signal output.
 
Damper rotation can be selectable direction ( CW or CCW ) by jumper PIN.
Damper moves by control signal that it maintains same position unless changing control signal.
When operating power is at normal and at no control signal, Actuator moves to the direction of "  
   0°" or " 90°" ( operating direction can be changd by jumper PIN ).
When power is OFF, Actuator will be stopped at current position.
 
 

 

ACT016-24

ACT016-24F

ACT016H-24

ACT016H-24F

사 용 전 원

24VAC ±20%, 60Hz 또는 24VDC ±10%

소 비 전 력

3.0VA at stand-by

5.5VA at 20Nm torque

7.0VA at full load

3.0VA at stand-by

9.0VA at 30Nm torque

10.5VA at full load

동 작 방 식

비례제어(proportional, modulation)

정 격 출 력

20Nm(200Kg-cm)

30Nm(300Kg-cm)

지 지 출 력

30Nm(300Kg-cm)

30Nm(300Kg-cm)

동 작 시 간

80 ∼ 150 sec

60 ∼ 100 sec

보 호 등 급

Dust proof and drip-proof(IEC IP53과 동급)

사 용 온 도

-15℃50℃

회 전 각 도

90°(90°에서 기계적으로 정지)

회 전 방 향

/역 방향(방향전환S/W내장)

결 선 단 자

내장단자대(AWG 26~18)

전선 인입구

PF1/2”(CTG16) x 1ea

보조 스위치

2 x SPST(250V,2A), “S” type만 해당

중량 및 크기

1.4Kg, 120mmx190mmx67mm(W x L x H)

 

축직접결합방식기어풀림기능,

One-touch Cover, 과전류방지 및 절전기능

 
Mounting Bracket : To mount Actuator on damper axis directly, it must be used with mounting bracket and fixing pin of mounting bracket should be correctly fixed on the groove of Actuator.
Mounting Location : Select easy location for setting dial of front side of Actuator and cable connection.
Manual Control : To adjust correct open/close function of switching location of damper, first to press manual button according to mounting procedures and adjust shaft adaptor and location indicator. 
Mechanical limitation for rotating degree movement : can be limited rotating degree movement by 5°between 0°to 90°.