Apiste Panel Cooling Units Standard ENC-AR422L-CU, AR620L-CU, AR1120L-CU, AR1652L-CU, AR2200L-CU, AR2900L-CU, G310EX, G320EX, G510EX, G710EX, G1110EX
Xuất sứ: Apiste
Nhà cung cấp: PITESCO Viet Nam
Hãng sản xuất: Apiste
ENC-AR422L-CU
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 400/450 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 45 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H450×W300×D115 |
Volume (kg) | 13 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200/Single-phase AC200 to 220 |
Consumption Current/Rating (A) | 1.8/1.7 |
Consumption Current/MAX (A) | 1.9/1.8 |
Starting Current (A) | 4.0/4.2 |
Consumption Voltage/Rating (W) | 295/330 |
Consumption Voltage/MAX (W) | 335/365 |
Noise Resistance | EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2 EN61000-6-2 EN61000-6-4 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 80g |
Noise (dB) | 59/61.5 |
External Output | Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A) |
Display | LED / RUN LED display / temperature error in the panel |
Regulatory Compliance | CE marking, Standard UL, Electrical Appliance and Material Safety Law |
Environmental Response | RoHS |
ENC-AR620L-CU
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 500/600 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H450×W350×D200 |
Volume (kg) | 16 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 1.8/1.6 |
Consumption Current/MAX (A) | 2.1/1.9 |
Starting Current (A) | 4.0/4.2 |
Consumption Voltage/Rating (W) | 280/270 |
Consumption Voltage/MAX (W) | 370/360 |
Noise Resistance | EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2 |
Vibration Resistance | JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 100g |
Noise (dB) | 63/67 |
External Output | Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A) |
Display | LED / RUN LED display / temperature error in the panel |
Regulatory Compliance | CE marking, Standard UL, Electrical Appliance and Material Safety Law |
Environmental Response | RoHS |
ENC-AR1120L-CU
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 950/1100 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H730×W300×D230 |
Volume (kg) | 23 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 2.6/2.4 |
Consumption Current/MAX (A) | 3.1/3.2 |
Starting Current (A) | 7.5/7.1 |
Consumption Voltage/Rating (W) | 440/460 |
Consumption Voltage/MAX (W) | 560/570 |
Noise Resistance | EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a |
Noise (dB) | 64/68 |
External Output | Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A) |
Display | LED / RUN LED display / temperature error in the panel |
Regulatory Compliance | CE marking, Standard UL, Electrical Appliance and Material Safety Law |
Environmental Response | RoHS |
ENC-AR1652L-CU
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 1450/1600 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 55 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H1000×W400×D230 |
Volume (kg) | 39 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 3.8/3.6 |
Consumption Current/MAX (A) | 4.7/4.6 |
Starting Current (A) | 16.5/15.5 |
Consumption Voltage/Rating (W) | 640/710 |
Consumption Voltage/MAX (W) | 830/900 |
Noise Resistance | EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 430g |
Noise (dB) | 68/72 |
External Output | Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A) |
Display | LED / RUN LED display / temperature error in the panel |
Regulatory Compliance | CE marking, Standard UL, Electrical Appliance and Material Safety Law |
Environmental Response | RoHS |
ENC-AR2200L-CU
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 2000/2200 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 55 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H1200×W450×D230 |
Volume (kg) | 48 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Three phase AC200 |
Consumption Current/Rating (A) | 3.4/3.2 |
Consumption Current/MAX (A) | 4.4/4.1 |
Starting Current (A) | 27/25 |
Consumption Voltage/Rating (W) | 815/950 |
Consumption Voltage/MAX (W) | 1100/1200 |
Noise Resistance | EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 570g |
Noise (dB) | 68/72 |
External Output | Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | CE marking, Standard UL, Electrical Appliance and Material Safety Law |
Environmental Response | RoHS |
ENC-AR2900L-CU
Mount Type | Side-mount |
---|---|
Cooling Capacity (W) | 2600/2900 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 55 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H1380×W450×D230 |
Volume (kg) | 57 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Three phase AC200 |
Consumption Current/Rating (A) | 4.9/4.6 |
Consumption Current/MAX (A) | 5.7/5.8 |
Starting Current (A) | 31/30 |
Consumption Voltage/Rating (W) | 1230/1430 |
Consumption Voltage/MAX (W) | 1570/1780 |
Noise Resistance | EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 580g |
Noise (dB) | 70/73 |
External Output | Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A) |
Display | LED / RUN LED display / temperature error in the panel |
Regulatory Compliance | CE marking, Standard UL, Electrical Appliance and Material Safety Law |
Environmental Response | RoHS |
ENC-G310EX
Mount Type | Roof-mount |
---|---|
Cooling Capacity (W) | 280/300 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H230×W590×D200 |
Volume (kg) | 16 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 3.4/3.2 |
Consumption Current/MAX (A) | 4.0/4.2 |
Starting Current (A) | 7.4/7.7 |
Consumption Voltage/Rating (W) | 290/310 |
Consumption Voltage/MAX (W) | 360/410 |
Noise Resistance | Fast Transient / LEVEL4 by burst immunity test |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 90g |
Noise (dB) | 62/65 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
ENC-G320EX
Mount Type | Roof-mount |
---|---|
Cooling Capacity (W) | 280/300 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H230×W590×D200 |
Volume (kg) | 16 Translate |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 1.8/1.5 |
Consumption Current/MAX (A) | 1.9/1.7 |
Starting Current (A) | 4.0/4.2 |
Consumption Voltage/Rating (W) | 280/265 |
Consumption Voltage/MAX (W) | 340/330 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 90g |
Noise (dB) | 62/65 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 4 (M6 x L12) |
---|---|
Exhaust Hose | 3m |
L-pipe | 2 |
INSULOK Tie | 6 |
Mounting nut | 4(M6) |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G320EX |
---|---|
External Fan | Air fan for G320EX |
Filter | ENC-F-28 |
Electrical Board | Substrate for AR310EX/AR320EX |
ENC-G510EX
Mount Type | Roof-mount |
---|---|
Cooling Capacity (W) | 450/500 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H230×W450×D250 |
Volume (kg) | 15 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 3.3/3.0 |
Consumption Current/MAX (A) | 3.6/3.9 |
Starting Current (A) | 7.4/7.7 |
Consumption Voltage/Rating (W) | 270/280 |
Consumption Voltage/MAX (W) | 320/360 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 90g |
Noise (dB) | 60/65 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 4 (M6 x L12) |
---|---|
Exhaust Hose | 3m |
L-pipe | 2 |
INSULOK Tie | 6 |
Mounting nut | 4(M6) |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G510EX |
---|---|
External Fan | Air fan for G510EX |
Filter | ENC-F-28 * 2 |
Electrical Board | Substrate for G510EX/G520EX |
ENC-G710EX
Mount Type | Roof-mount |
---|---|
Cooling Capacity (W) | 600/700 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H332×W550×D270 |
Volume (kg) | 22 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 3.2/3.3 |
Consumption Current/MAX (A) | 3.9/4.1 |
Starting Current (A) | 7.4/7.7 |
Consumption Voltage/Rating (W) | 250/300 |
Consumption Voltage/MAX (W) | 350/390 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 150g |
Noise (dB) | 60/65 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 4 (M6 x L12) |
---|---|
Exhaust Hose | 3m |
L-pipe | 2 |
INSULOK Tie | 6 |
Mounting nut | 4(M6) |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G710EX |
---|---|
External Fan | Air fan for G710EX |
Filter | ENC-F-21 * 2 |
Electrical Board | Substrate for G710EX/G720EX |
ENC-G1110EX
Mount Type | Roof-mount |
---|---|
Cooling Capacity (W) | 950/1100 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H318×W600×D353 |
Volume (kg) | 27 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC100 |
Consumption Current/Rating (A) | 5.4/4.8 |
Consumption Current/MAX (A) | 6.3/6.6 |
Starting Current (A) | 15.6/14.7 |
Consumption Voltage/Rating (W) | 440/470 |
Consumption Voltage/MAX (W) | 570/630 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 240g |
Noise (dB) | 60/65 |
External Output | Alarm output (a contact: No-voltage resistive load 250V 2A) |
Display | LED RUN LED display / temperature error in the panel |
Regulatory Compliance | EN60335-1 EN60335-2-40/EN61000-6-2 EN61000-6-4 |
Environmental Response | RoHS |
Parts list supplied
Mounting Bolt | 4 (M6 x L12) |
---|---|
Exhaust Hose | 3m |
L-pipe | 2 |
INSULOK Tie | 6 |
Washer | 2(M6) |
Wind Direction Louver | 1 |
Mounting nut | M4 * 2 /M6 * 4 |
User Manual | 1 |
Maintenance Parts List
Internal Circulation Fan | Circulation fan for G1110EX |
---|---|
External Fan | Air fan for G1110EX |
Filter | ENC-F-21 * 2 |
Electrical Board | Substrate for G1110EX/G1120EX |
ENC-AR520EX-CU
Mount Type | Roof-mount |
---|---|
Cooling Capacity (W) | 450/500 |
Setting Temperature Range (°C) | 25 to 45 |
Use Area Temperature (°C) | 20 to 50 |
Use Area Humidity (%RH) | 10-85(No condensation) |
External Dimensions (mm) | H230×W450×D250 |
Volume (kg) | 15 |
Coating Color | Color Munsell 5Y7 / 1 light beige |
Voltage Rating (V) | Single-phase AC200 |
Consumption Current/Rating (A) | 1.9/1.4 |
Consumption Current/MAX (A) | 2.0/1.8 |
Starting Current (A) | 4.0/4.2 |
Consumption Voltage/Rating (W) | 280/260 |
Consumption Voltage/MAX (W) | 360/320 |
Noise Resistance | EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2 |
Vibration Resistance | Equivalent to JIS Z 0200 Level1 |
Dust & Water Protection Grade | Equivalent to IP54 (internal circulation route) |
Coolant / Filling (g) | HFC-134a 90g |
Noise (dB) | 60/65 |
External Output | Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A) |
Display | LED / RUN LED display / temperature error in the panel |
Regulatory Compliance | CE marking, Standard UL, Electrical Appliance and Material Safety Law |
Environmental Response | RoHS |