apiste-precision-air-pau-a2600s-hc.png

Specifications

Cooling Method Air-Cooled Type
Type Temperature and humidity Controller
Cooling Capacity (W) 2100/2450
Heating Capacity (W) 4500
Humidifying Capacity (kg/h) 11.7
Temperature Control Precision (°C) +-0.2
Setting Temperature Range (°C) 20~30
Humidity Control Precision (%RH) +-1.0
Setting Humidity Range (%RH) 40~80
Use Area Temperature (°C) 20 ~ 35 (change in temperature gradient: within 1°C/1h)
Use Area Humidity (%RH) 10 ~ 85 (change in temperature gradient: within 5%/1h) (No condensation)
Processed Air Volume (m2/min)(50Hz) 8.0/8.5
External Dimensions(mm) H1065×W450×D900
Volume (kg) 120
Coating Color Ivory (JPMA: Semi-gloss Y22-85B)
Blower Duct Connection Diameter (mm) φ150 with damper
Rated Voltage (V) Three-phase AC200
Consumption Current (A) 5.0/4.7(MIN) 41.5/41.9(MAX)
Wattage (W) 920/1100(MIN) 15000(MAX)
Humidifier/Water Supply Volume (ℓ/h) 13.5
Humidifier/Water Supply Pressure (MPa) 0.03-0.5
Water Supply Temperature (°C) 0-50
Humidifier/Water Supply Connection Diameter (mm) 15A female socket (Rc: 1/2 inch)
Drain Discharge Water Connection Diameter (mm) 20A female socket (Rc: 3/4 inch)
Coolant R-134a 560g
Exhaust Air Volume (m3/min) 16.0/18.8
Safety Circuit/Main Circuit Earth leakage circuit breaker (50A 30mA), Prevent reversal relay
Safety Circuit/Blower Overcurrent relay (0.9A), Delay timer (3 minutes), Surge Absorber
Safety Circuit/Compressor Overcurrent relay, motor protectors, surge absorbers, low temperature thermostat driving prevention
Safety Circuit/Heater Thermostat to prevent overheating (65°C OFF 55°C ON), thermal fuse (99°C), surge absorber
Safety Circuit/Humidifier Float switch, thermostat to prevent overheating (120°C +- 10 ℃ OFF), fuse temperature (119°C), automatic timer drainage, drainage manual switch, surge absorber
Output/Main Unit Malfunction Output No-voltage contact a (AC250V / 3A / Resistive load)
Output/Temperature Control Top-Bottom Limit Alarm No-voltage contact a (AC250V / 3A / Resistive load)
Output/Humidity Control Top-Bottom Limit Alarm No-voltage contact a (AC250V / 3A / Resistive load)

Dimensions

404_ext_82_en_0_S.png

 

Sensor dimensions

404_ext_85_en_0_S.png

Temperature & Humidity Control Range Chart

404_ext_88_en_0_S.png