apiste-precision-air-pau-az1800se.png

Specifications

 

Cooling Method Air-Cooled Type
Type Temperature Controller (energy conservation)
Cooling Capacity (W) 1300/1500
Heating Capacity (W) 1900/2100
Temperature Control Precision (°C) +-0.1
Setting Temperature Range (°C) 11~42
Use Area Temperature (°C) 15~35 (change in temperature gradient: within 1°C/1h)
Use Area Humidity (%RH) 15~85(change in temperature gradient: within 5%/1h) (No condensation)
Processed Air Volume (m2/min)(50Hz) 4.8/5.0
External Dimensions(mm) H1065×W400×D650
Volume (kg) 75
Coating Color Ivory(JPMA: Semi-gloss Y22-85B)
Blower Duct Connection Diameter (mm) φ100 with damper
Rated Voltage (V) Three-phase AC200
Consumption Current (A) 3.1/2.6
Wattage (W) 650/750
Drain Discharge Water Connection Diameter (mm) 20A Female socket (Rp3/4)
Coolant HFC-134a 290g
Exhaust Air Volume (m3/min) 10/12
Safety Circuit/Main Circuit Earth leakage circuit breaker(10A 30mA)
Safety Circuit/Blower Overcurrent relay, delay timer (3 minutes), surge absorber, thermal overload protector
Safety Circuit/Compressor Anti-freezing mechanism cooler prevention, overcurrent relay, motor protectors, surge absorber
Output/Main Unit Malfunction Output No-voltage contact a (AC250V / 2A / Resistive load)
Output/Temperature Control Top-Bottom Limit Alarm No-voltage contact a (AC250V / 2A / Resistive load)

Dimensions

2591_ext_82_en_0_S.jpg

Temperature Control Range Chart

[Range: temperature control *1]
Range showed a correlation between temperature and ambient temperature the unit can be configured.
Temperature control accuracy of this unit (+- 0.5 °C) is applied to the set temperature within this range.
[Range: temperature control *2]
Although outside the scope of warranty (+- 0.5 °C) temperature control accuracy, range and showed a correlation of temperature and ambient temperature the unit can be configured.
*Measurement conditions
AC100V 60Hz (1) single-phase power supply:
Ambient humidity: 40% RH (2)
Blowing air volume: 1.0m 3 / min (3)
Sensor is mounted in the body of the performance of the outlet air outlet body (4)
The body, without mounting the fan duct (5)