apiste-panel-cooling-units-standard-enc-ar720ex-cu-ar1120ex-cu-ar1652ex-cu-ar2200ex-cu-ar2900ex-cu-1.png

ENC-AR720EX-CU

ENC-AR720EX-CU

Mount Type Roof-mount
Cooling Capacity (W) 600/700
Setting Temperature Range (°C) 25 to 45
Use Area Temperature (°C) 20 to 50
Use Area Humidity (%RH) 10-85(No condensation)
External Dimensions (mm) H333×W550×D270
Volume (kg) 22
Coating Color Color Munsell 5Y7 / 1 light beige
Voltage Rating (V) Single-phase AC200
Consumption Current/Rating (A) 1.9/1.4
Consumption Current/MAX (A) 2.0/1.8
Starting Current (A) 4.0/4.2
Consumption Voltage/Rating (W) 285/265
Consumption Voltage/MAX (W) 340/350
Noise Resistance EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2
Vibration Resistance Equivalent to JIS Z 0200 Level1
Dust & Water Protection Grade Equivalent to IP54 (internal circulation route)
Coolant / Filling (g) HFC-134a 150g
Noise (dB) 60/65
External Output Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A)
Display LED / RUN LED display / temperature error in the panel
Regulatory Compliance CE marking, Standard UL, Electrical Appliance and Material Safety Law
Environmental Response RoHS

 

ENC-AR1120EX-CU

ENC-AR1120EX-CU

Mount Type Roof-mount
Cooling Capacity (W) 950/1100
Setting Temperature Range (°C) 25 to 45
Use Area Temperature (°C) 20 to 50
Use Area Humidity (%RH) 10-85(No condensation)
External Dimensions (mm) H318×W600×D353
Volume (kg) 27
Coating Color Color Munsell 5Y7 / 1 light beige
Voltage Rating (V) Single-phase AC200
Consumption Current/Rating (A) 2.7/2.4
Consumption Current/MAX (A) 3.2/3.3
Starting Current (A) 7.5/7.1
Consumption Voltage/Rating (W) 440/470
Consumption Voltage/MAX (W) 570/630
Noise Resistance EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2
Vibration Resistance Equivalent to JIS Z 0200 Level1
Dust & Water Protection Grade Equivalent to IP54 (internal circulation route)
Coolant / Filling (g) HFC-134a 240g
Noise (dB) 60/65
External Output Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A)
Display LED / RUN LED display / temperature error in the panel
Regulatory Compliance CE marking, Standard UL, Electrical Appliance and Material Safety Law
Environmental Response RoHS

 

ENC-AR1652EX-CU

ENC-AR1652EX-CU

Mount Type Roof-mount
Cooling Capacity (W) 1500/1650
Setting Temperature Range (°C) 25 to 45
Use Area Temperature (°C) 20 to 55
Use Area Humidity (%RH) 10-85(No condensation)
External Dimensions (mm) H448×W590×D350
Volume (kg) 39
Coating Color Color Munsell 5Y7 / 1 light beige
Voltage Rating (V) Single-phase AC200
Consumption Current/Rating (A) 3.6/3.5
Consumption Current/MAX (A) 4.4/4.5
Starting Current (A) 16.5/15.5
Consumption Voltage/Rating (W) 630/690
Consumption Voltage/MAX (W) 800/860
Noise Resistance EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2
Vibration Resistance Equivalent to JIS Z 0200 Level1
Dust & Water Protection Grade Equivalent to IP54 (internal circulation route)
Coolant / Filling (g) HFC-134a 440g
Noise (dB) 65/68
External Output Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A)
Display LED / RUN LED display / temperature error in the panel
Regulatory Compliance CE marking, Standard UL, Electrical Appliance and Material Safety Law
Environmental Response RoHS

 

ENC-AR2200EX-CU

ENC-AR2200EX-CU

Mount Type Roof-mount
Cooling Capacity (W) 1900/2200
Setting Temperature Range (°C) 25 to 45
Use Area Temperature (°C) 20 to 55
Use Area Humidity (%RH) 10-85(No condensation)
External Dimensions (mm) H447×W650×D400
Volume (kg) 48
Coating Color Color Munsell 5Y7 / 1 light beige
Voltage Rating (V) Three phase AC200
Consumption Current/Rating (A) 3.3/3.2
Consumption Current/MAX (A) 4.2/4.1
Starting Current (A) 27/25
Consumption Voltage/Rating (W) 850/1050
Consumption Voltage/MAX (W) 1050/1250
Noise Resistance EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2
Vibration Resistance Equivalent to JIS Z 0200 Level1
Dust & Water Protection Grade Equivalent to IP54 (internal circulation route)
Coolant / Filling (g) HFC-134a 575g
Noise (dB) 70/71
External Output Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A)
Display LED / RUN LED display / temperature error in the panel
Regulatory Compliance CE marking, Standard UL, Electrical Appliance and Material Safety Law
Environmental Response RoHS

 

ENC-AR2900EX-CU

ENC-AR2900EX-CU

Mount Type Roof-mount
Cooling Capacity (W) 2600/2900
Setting Temperature Range (°C) 25 to 45
Use Area Temperature (°C) 20 to 55
Use Area Humidity (%RH) 10-85(No condensation)
External Dimensions (mm) H447×W760×D400
Volume (kg) 57
Coating Color Color Munsell 5Y7 / 1 light beige
Voltage Rating (V) Three phase AC200
Consumption Current/Rating (A) 4.8/4.7
Consumption Current/MAX (A) 5.7/5.8
Starting Current (A) 31/30
Consumption Voltage/Rating (W) 1270/1450
Consumption Voltage/MAX (W) 1700/1900
Noise Resistance EN61000-3-2 EN61000-3-3 EN55014-1 EN55014-2
Vibration Resistance 5Hz frequency 20mm total amplitude
Dust & Water Protection Grade Equivalent to IP54 (internal circulation route)
Coolant / Filling (g) HFC-134a 775g
Noise (dB) 72/73
External Output Alarm output output / cooling operation (a contact: No-voltage resistive load 250V 2A)
Display LED / RUN LED display / temperature error in the panel
Regulatory Compliance CE marking, Standard UL, Electrical Appliance and Material Safety Law
Environmental Response RoHS

 

Cooling capacity) Note: 35°C ambient temperature, the rated capacity of 35°C when the set temperature inside the panel.
(Method: JIS-C-9612 air enthalpy measurement conditions)
Ambient humidity / ambient temperature is not meant to satisfy all conditions in temperature and humidity.
RH 40% when the value of the maximum allowed ambient temperature, ambient humidity using an ambient temperature of use: The value MAX.
CE marking requirements in: noise resistance.
Please read instructions carefully before use, please use properly.